Section 51-54A-1205 - Section 1205-Solar photovoltaic power systems
1205.1General. Installation, modification, or alteration of solar photovoltaic power systems shall comply with this section. Due to the emerging technologies in the solar photovoltaic industry, it is understood fire code officials may need to amend prescriptive requirements of this section to meet the requirements for firefighter access and product installations. Section 104.10 Alternative materials and methods of this code shall be considered when approving the installation of solar photovoltaic power systems. Solar photovoltaic power systems shall be installed in accordance with Sections 1205.2.1 through 1205.6, the International Building Code, and chapter 19.28 RCW.
1205.2.1Solar photovoltaic systems for Group R-3 residential and buildings built under the International Residential Code. Solar photovoltaic systems for Group R-3 residential and buildings built under the International Residential Code shall comply with Sections 1205.2.1.1 through 1205.2.3.

EXCEPTIONS:

1. Residential dwellings with an approved automatic fire sprinkler system installed.

2. Residential dwellings with approved mechanical or passive ventilation systems.

3. Where the fire code official determines that the slope of the roof is too steep for emergency access.

4. Where the fire code official determines that vertical ventilation tactics will not be utilized.

5. These requirements shall not apply to roofs where the total combined area of the solar array does not exceed 33 percent as measured in plan view of the total roof area of the structure, where the solar array will measure 1,000 sq. ft. or less in area, and where a minimum 18 inches unobstructed pathway shall be maintained along each side of any horizontal ridge.

1205.6Size of solar photovoltaic array.
1. Each photovoltaic array shall be limited to 150 feet (45,720 mm) by 150 feet (45,720 mm). Multiple arrays shall be separated by a 3-foot wide (914 mm) clear access pathway.
2. Panels/modules shall be located up to the roof ridge where an alternative ventilation method approved by the fire code official has determined vertical ventilation techniques will not be employed.

Wash. Admin. Code § 51-54A-1205

Adopted by WSR 22-13-093, Filed 6/14/2022, effective 7/1/2023
Amended by WSR 23-23-106, Filed 11/15/2023, effective 3/16/2024