EXCEPTIONS: | 1. Factory-built commercial exhaust hoods that are listed and labeled in accordance with UL 710, and installed in accordance with Section 304.1 of the International Mechanical Code, shall not be required to comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3, 507.4, and 507.5 of the International Mechanical Code. |
2. Factory-built commercial cooking recirculating systems that are listed and labeled in accordance with UL 710B, and installed in accordance with Section 304.1 of the International Mechanical Code, shall not be required to comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3, 507.4, and 507.5 of the International Mechanical Code. Spaces in which such systems are located shall be considered to be kitchens and shall be ventilated in accordance with Table 403.3.1.1 of the International Mechanical Code. For the purpose of determining the floor area required to be ventilated, each individual appliance shall be considered as occupying not less than 100 square feet (9.3 m2). | |
3. Where cooking appliances are equipped with integral down-draft exhaust systems and such appliances and exhaust systems are listed and labeled for the application in accordance with NFPA 96, a hood shall not be required at or above them. | |
4. A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm (0.236 m3/s) in accordance with UL 710B. | |
5. A Type I hood shall not be required to be installed in an R-2 occupancy with not more than 16 residents. |
Table 606.2.1
Type of Hood Required for Domestic Cooking Appliances in the Following Spacesa,b
Type of Space | Type of Cooking | Type of Hood |
Church | 1. Boiling, steaming, and warming precooked food 2. Roasting, pan frying, and deep frying | Residential hoodcor Type II hood Type I hood |
Community or party room in apartment and condominium | 1. Boiling, steaming, and warming precooked food 2. Roasting, pan frying, and deep frying | Residential hoodcor Type II hoodd Type I hood |
Day care | 1. Boiling, steaming, and warming precooked food 2. Roasting, pan frying, and deep frying | Residential hoodcor Type II hoodd Type I hood |
Dormitory, assisted living facility, nursing home | 1. Boiling, steaming, and warming precooked food 2. Roasting, pan frying, and deep frying | Residential hoodcor Type II hood Type I hood |
Office lunch room | 1. Boiling, steaming, and warming precooked food 2. Roasting, pan frying, and deep frying | Residential hoodcor Type II hoodd Type I hood |
a Commercial cooking appliances shall comply with Section 507.2 of the International Mechanical Code.
b Requirements in this table apply to electric or gas fuel appliances only. Solid fuel appliances or charbroilers require Type I hoods.
c Residential hood shall ventilate to the outside.
d Type II hood required when more than one appliance is used.
Wash. Admin. Code § 51-54A-0606