Section 51-52-1106 - Section 1106-Machinery room, special requirements1106.4.2Emergency ventilation system. An emergency ventilation system shall be provided at the minimum exhaust rate specified in ASHRAE 15 or Table 1106.4.2. Shutdown of the emergency ventilation system shall be by manual means. Table 1106.4.2
MINIMUM EXHAUST RATES
Refrigerant | Q(m/sec) | Q(cfm) |
R32 | 15.4 | 32,600 |
R143A | 13.6 | 28,700 |
R444A | 6.46 | 13,700 |
R444B | 10.6 | 22,400 |
R445A | 7.83 | 16,600 |
R446A | 23.9 | 50,700 |
R447A | 23.8 | 50,400 |
R451A | 7.04 | 15,000 |
R451B | 7.05 | 15,000 |
R1234yf | 7.80 | 16,600 |
R1234ze(E) | 5.92 | 12,600 |