Wash. Admin. Code § 51-52-0507

Current through Register Vol. 24-23, December 1, 2024
Section 51-52-0507 - Section 507-Commercial kitchen hoods

507.1.2 Domestic cooking appliances used for commercial purposes. Domestic cooking appliances utilized for commercial purposes shall be provided with Type I, Type II or residential hoods as required for the type of appliances and processes in accordance with Table 507.1.2 and Sections 507.2 and 507.3. Domestic cooking appliances utilized for domestic purposes shall comply with Section 505.

TABLE 507.1.2

TYPE OF HOOD REQUIRED FOR DOMESTIC COOKING APPLIANCES IN THE FOLLOWING SPACESa, b

Type of SpaceType of CookingType of Hood
Church1. Boiling, steaming and warming precooked food 2. Roasting, pan frying and deep frying Type II hood Type I hood
Community or party room in apartment and condominium1. Boiling, steaming and warming precooked food 2. Roasting, pan frying and deep frying Residential hoodc or Type II hoodd Type I hood
Day care1. Boiling, steaming and warming precooked food 2. Roasting, pan frying and deep frying Residential hoodc or Type II hoodd Type I hood
Dormitory, boarding home, nursing home1. Boiling, steaming and warming precooked food 2. Roasting, pan frying and deep frying Type II hood Type I hood
Office lunch room1. Boiling, steaming and warming precooked food 2. Roasting, pan frying and deep frying Residential hoodc or Type II hoodd Type I hood

a Commercial cooking appliances shall comply with Section 507.2.

b Requirements in this table apply to electric or gas fuel appliances only. Solid fuel appliances or charbroilers require Type I hoods.

c Residential hood shall ventilate to the outside.

d Type II hood required when more than one appliance is used.

507.2 Type I hoods. Type I hoods shall be installed where cooking appliances produce grease or smoke as a result of the cooking process. Type I hoods shall be installed over medium-duty, heavy-duty and extra-heavy-duty cooking appliances.

EXCEPTIONS:1. A Type I hood shall not be required for an electric cooking appliance where an approved testing agency provides documentation that the appliance effluent contains 5 mg/m3 or less of grease when tested at an exhaust flow rate of 500 cfm in accordance with Section 17 of UL 710B.
2. A Type I hood shall not be required in an R-2 type occupancy with not more than 16 residents.

Wash. Admin. Code § 51-52-0507

Amended by WSR 16-01-148, Filed 12/21/2015, effective 7/1/2016

Statutory Authority: RCW 19.27.031, 19.27.074 and chapters 19.27 and 34.05 RCW. 13-04-053, § 51-52-0507, filed 2/1/13, effective 7/1/13. Statutory Authority: RCW 19.27.190, 19.27.074, 19.27.031 and chapters 19.27 and 34.05 RCW. 10-03-099, § 51-52-0507, filed 1/20/10, effective 7/1/10.