Basements located more than 4 feet below grade level shall not be used for family home child care unless one of following conditions exist:
Floors located more than 4 feet above grade level shall not be occupied by children in family home child care.
EXCEPTIONS: | 1. Use of toilet facilities while under supervision of an adult staff person; 2. Family home child care may be allowed on the second story if one of the following conditions exists: 2.1. Stairways from the second story open directly to the exterior of the building without entering the first floor; 2.2. One of the two required means of egress discharges directly to the exterior from the second story level, and a self-closing door is installed at the top or bottom of the interior stair leading to the floor below; or 2.3. An automatic residential sprinkler system shall be designed and installed in accordance with Section P2904 or NFPA 13D. |
Every sleeping or napping room in a family home child care shall have at least one operable window for emergency rescue.
EXCEPTION: | Sleeping or napping rooms having doors leading to two separate means of egress, or a door leading directly to the exterior of the building. |
Rooms or spaces containing a commercial-type cooking kitchen, boiler, maintenance shop, janitor closet, laundry, woodworking shop, flammable or combustible storage, or painting operation shall be separated from the family home child care area by at least 1-hour fire-resistant construction.
EXCEPTION: | A fire-resistant separation shall not be required where the food preparation kitchen contains only a domestic cooking range, and the prepod does not result in the production of smoke or grease laden vapors. |
Smoke alarms shall be installed in accordance with the requirements of new construction per Section R314. In addition to the required smoke alarms, a heat alarm shall be provided in each kitchen.
EXCEPTION: | Subject to approval of the code official, a sprinkler system is not required where all of the following conditions are met: 1. Child care areas are located on a floor within 4 feet of grade level; 2. Each room used for child care shall have a door compliant with Section R311.2 and R311.3, leading directly to the exterior of the building. The exterior landing at the door shall comply with Section R311.3 but need not comply with Section R311.3.1. |
Wash. Admin. Code § 51-51-0331