The following shall have automatic receptacle control complying with Section C405.10.1:
EXCEPTION: | Automatic receptacle controls are not required for the following: 1. Receptacles specifically designated for equipment requiring continuous operation (24 hours per day, 365 days per year). 2. Spaces where an automatic control would endanger the safety or security of the room or building occupants. 3. Within a single modular office workstation, noncontrolled receptacles are permitted to be located more than 12 inches (304.8 mm), but not more than 72 inches (1828 mm) from the controlled receptacles serving that workstation. |
Wash. Admin. Code § 51-11C-40510
Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-40510, filed 2/1/13, effective 7/1/13.