EXCEPTIONS: | 1. Exhaust air and outdoor air connections to isolation areas where the fan system to which they connect is not greater than 5,000 cfm (2360 L/s). 2. Exhaust airflow from a single isolation area of less than 10 percent of the design airflow of the exhaust system to which it connects. 3. Isolation areas intended to operate continuously or intended to be inoperative only when all other isolation areas in a zone are inoperative. |
Wash. Admin. Code § 51-11C-40321
Statutory Authority: RCW 19.27A.020, 19.27A.025 and chapters 19.27 and 34.05 RCW. 13-04-056, § 51-11C-40321, filed 2/1/13, effective 7/1/13.