Wash. Admin. Code § 296-99-080

Current through Register Vol. 24-23, December 1, 2024
Section 296-99-080 - How must continuous-flow bulk raw grain dryers be equipped and installed?
(1) You must ensure that all direct-heat grain dryers have automatic controls that:
(a) Shut off the fuel supply in case of power, flame, or ventilation airflow shutoff; and
(b) Stop the grain flow into the dryer if the dryer exhaust gets too hot.
(2) You must ensure that each direct-heat grain dryer installed after March 30, 1988, is:
(a) Located outside the grain elevator; or
(b) When located inside the grain elevator, protected by a fire or explosion suppression system; or
(c) Isolated by a structure with at least a one hour fire-resistance rating.

Wash. Admin. Code § 296-99-080

Amended by WSR 17-16-132, Filed 8/1/2017, effective 9/1/2017

Statutory Authority: Chapter 49.17 RCW. 97-22-065, § 296-99-080, filed 11/3/97, effective 1/1/98; 88-23-054 (Order 88-25), § 296-99-080, filed 11/14/88.