Section 296-835-099 - Definitions

ACGIH. American Conference of Governmental Industrial Hygienists.

Adjacent area. Any area within twenty feet (6.1 m) of a vapor area that is not separated from the vapor area by tight partitions.

ANSI. American National Standards Institute.

Approved. Approved or listed by a nationally recognized testing laboratory. Refer to federal regulation 29 C.F.R. 1910.7, for definition of nationally recognized testing laboratory.

Autoignition temperature. The minimum temperature required to cause self-sustained combustion without any other source of heat.

Detearing. A process for removing excess wet coating material from the bottom edge of a dipped or coated object or material by passing it through an electrostatic field.

Dip tank. A container holding a liquid other than plain water that is used for dipping or coating. An object may be immersed (or partially immersed) in a dip tank or it may be suspended in a vapor coming from the tank.

Flammable liquid. Any liquid having a flashpoint at or below 199.4°F (93°C). Flammable liquids are divided into four categories as follows:

(a) Category 1 shall include liquids having flashpoints below 73.4°F (23°C) and having a boiling point at or below 95°F (35°C).

(b) Category 2 shall include liquids having flashpoints below 73.4°F (23°C) and having a boiling point above 95°F (35°C).

(c) Category 3 shall include liquids having flashpoints at or above 73.4°F (23°C) and at or below 140°F (60°C). When a Category 3 liquid with a flashpoint at or above 100°F (37.8°C) is heated for use to within 30°F (16.7°C) of its flashpoint, it shall be handled in accordance with the requirements for a Category 3 liquid with a flashpoint below 100°F (37.8°C).

(d) Category 4 shall include liquids having flashpoints above 140°F (60°C) and at or below 199.4°F (93°C). When a Category 4 flammable liquid is heated for use to within 30°F (16.7°C) of its flashpoint, it shall be handled in accordance with the requirements for a Category 3 liquid with a flashpoint at or above 100°F (37.8°C).

(e) When liquid with a flashpoint greater than 199.4°F (93°C) is heated for use to within 30°F (16.7°C) of its flashpoint, it shall be handled in accordance with the requirements for a Category 4 flammable liquid.

Flashpoint. The minimum temperature at which a liquid gives off a vapor within a test vessel in sufficient concentration to form an ignitable mixture with air near the surface of the liquid, and shall be determined as follows:

(a) The flashpoint of liquids having a viscosity less than 45 Saybolt universal second(s) at 100°F (37.8°C) and a flashpoint below 175°F (79.4°C) shall be determined in accordance with the Standard Method of Test for Flashpoint by the Tag Closed Tester, ASTM D-56-69 (incorporated by reference; WAC 296-901-14024, Appendix B-Physical hazard criteria).

(b) The flashpoints of liquids having a viscosity of 45 Saybolt universal second(s) or more at 175°F (79.4°C) or higher shall be determined in accordance with the Standard Method of Test for Flashpoint by the Pensky Martens Closed Tester, ASTM D-93-69 (incorporated by reference; WAC 296-901-14024, Appendix B-Physical hazard criteria).

Lower flammable limit. The lowest concentration of a material that will propagate a flame. The LFL is usually expressed as a percent by volume of the material in air (or other oxidant).

NFPA. National Fire Protection Association.

Vapor area. Any area in the vicinity of dip tanks, their drain boards or associated drying, conveying, or other equipment where the vapor concentration could exceed twenty-five percent of the lower flammable limit (LFL) for the liquid in the tank.

You. The employer. See the definition of employer in the safety and health core rules, WAC 296-800-370.

Wash. Admin. Code § 296-835-099

Adopted by WSR 17-18-075, Filed 9/5/2017, effective 10/6/2017