Wash. Admin. Code § 296-826-40050

Current through Register Vol. 24-23, December 1, 2024
Section 296-826-40050 - Other refrigerated storage equipment
(1) You must discharge ammonia to storage by using either:
(a) A receiver with an automatic float valve;

or

(b) A high pressure liquid drain trap of suitable capacity.
(2) You must make sure receivers are:
(a) Designed for at least 250 psig;

and

(b) Equipped with all of the following:
(i) Necessary connections;
(ii) Safety relief valves;
(iii) Gauging devices.
(3) You must cover insulated containers and pipelines with material that meets all of the following:
(a) Thick enough for the temperatures it will be exposed to;
(b) Supported;
(c) Weather and fire resistant.

Wash. Admin. Code § 296-826-40050

Amended by WSR 15-23-086, Filed 11/17/2015, effective 12/18/2015

Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 06-10-067, § 296-826-40050, filed 5/2/06, effective 9/1/06.