You must meet the requirements ... | in this section: |
Nonrefrigerated containers | WAC 296-826-60030 |
Refrigerated tanks | WAC 296-826-60035 |
Welding | WAC 296-826-60040 |
You must make sure filling densities for non refrigerated containers are below or equal to the requirements in Table 15, Filling Densities.
Table 15 Filling Densities
Containers | Aboveground Containers | Underground Containers |
Uninsulated | 56% | 58% |
Insulated | 57% | _____ |
Note: | For uninsulated, aboveground containers, the 56% corresponds to: |
1.82% by volume at -28°F. | |
2. 85% by volume at 5°F. | |
3. 87.5% by volume at 30°F. | |
4. 90.6% by volume at 60°F. |
Wash. Admin. Code § 296-826-60030
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 06-10-067, § 296-826-60030, filed 5/2/06, effective 9/1/06.