Wash. Admin. Code § 296-818-40010

Current through Register Vol. 24-23, December 1, 2024
Section 296-818-40010 - Explosion venting and wiring

You must follow the requirements in Table-3 for flammable or combustible dust mixtures.

Table-3: Explosion Venting and Wiring

If you haveThen

Flammable or explosive dust mixtures that may be present

Make sure the construction of equipment, including the exhaust system and all electrical wiring, meets both of the following:

* The American National Standard Installation (ANSI) of Blower and Exhaust Systems for Dust, Stock, and Vapor Removal or Conveying, NFPA 91. 2004.

* The electrical requirements for Class II locations in WAC 296-24-95613, located in Part L of chapter 296-24 WAC.

Make sure blast cleaning enclosures, the ducts, and the dust collector are constructed with either loose panels or explosion venting areas that meet all of the following:

* Provides pressure relief in case of an explosion.

* Are located away from occupied areas.

* The Guide for Deflagations, NFPA 68. 2002.

Wash. Admin. Code § 296-818-40010

Amended by WSR 17-18-075, Filed 9/5/2017, effective 10/6/2017

Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 06-12-074, § 296-818-40010, filed 6/6/06, effective 9/1/06.