This section applies to equipment that operates at 600 volts or less.
Note: | * Other equipment associated with the electrical installation and located above or below the electric equipment may extend not more than 6 inches beyond the front of the electric equipment. |
This table shows the area you must keep clear depending on the layout of the electrical equipment.
Table XX
Conditions2 | Minimum Clear Distance3 | Minimum Clear Distance3 |
0 - 150 volts to ground | 151 - 600 volts to ground | |
A1 | 3 ft. | 3 ft. |
B | 3 ft.1 | 3 1/2 ft. |
C | 3 ft. | 4 ft. |
A = Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by suitable wood or other insulating material. Insulated wire or insulated bus bars operating at not over 300 volts aren't considered live parts.
B = Exposed live parts on one side and grounded parts on the other side.
C = Exposed live parts on both sides of the workspace (not guarded as provided in condition A with the operator between the panels).
Wash. Admin. Code § 296-800-28027
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060, and chapter 49.17 RCW. 12-16-064, § 296-800-28027, filed 7/31/12, effective 9/1/12.