Wash. Admin. Code § 296-307-48023

Current through Register Vol. 24-23, December 1, 2024
Section 296-307-48023 - Fuel-gas manifolds
(1) Manifolds must be approved either separately for each component part or as an assembled unit.
(2) Fuel-gas cylinders connected to one manifold inside a building must be limited to a maximum total capacity of 300 pounds of LP-gas or 3,000 cubic feet of other fuel-gas. More than one such manifold with connected cylinders may be located in the same room if the manifolds are at least 50 feet apart or separated by a noncombustible barrier at least 5 feet high having a fire-resistance rating of at least one-half hour.
(3) Exception: Fuel-gas cylinders connected to one manifold having an aggregate capacity exceeding 300 pounds of LP-gas or 3,000 cubic feet of other fuel-gas must be located outdoors, or in a separate building or room constructed according to 252 (a)(8) and (9) C.F.R.
(4) Separate manifold buildings or rooms may also be used for the storage of drums of calcium carbide and cylinders containing fuel gases as provided in WAC 296-307-48007. Such buildings or rooms must have no open flames for heating or lighting and must be well ventilated.
(5) High-pressure fuel-gas manifolds must have approved pressure regulating devices.

Wash. Admin. Code § 296-307-48023

Amended by WSR 20-21-091, Filed 10/20/2020, effective 11/20/2020

Statutory Authority: RCW 49.17.040. 98-24-096, § 296-307-48023, filed 12/1/98, effective 3/1/99. 97-09-013, recodified as § 296-307-48023, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and[49.17.]060 . 96-22-048, § 296-306A-48023, filed 10/31/96, effective 12/1/96.