OR
Exemption: | An automatic fire extinguishing system or an automatic dip tank cover is not required for a hardening or tempering tank that: 1. Holds less than five hundred gallons; OR 2. Has less than twenty-five square feet of liquid surface area. |
Table 1: Automatic Fire Protection System Requirements
If the employer provides: | The employer must: |
An automatic fire extinguishing system | * Use extinguishing materials suitable for a fire fueled by the liquid in the tank * Make sure the system protects the: -Tanks -Drain boards -Stock over drain boards. |
A dip tank cover | * Make sure the cover is: -Closed by approved automatic devices in the event of fire -Able to be manually activated -Kept closed when the tank is not being used -Made of noncombustible material or metal-clad material with locked metal joints. |
Wash. Admin. Code § 296-307-45525
Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. 03-10-068, § 296-307-45525, filed 5/6/03, effective 8/1/03.