Wash. Admin. Code § 296-307-44005

Current through Register Vol. 24-23, December 1, 2024
Section 296-307-44005 - Valves and accessories
(1) A filling connection on the container must be fitted with one of the following:
(a) A combination back-pressure check and excess flow valve.
(b) One double or two single back-pressure valves.
(c) A positive shut-off valve, in conjunction with either:
(i) An internal back-pressure valve; or
(ii) An internal excess flow valve.

Instead of an excess flow valve, filling connections may be fitted with a quick-closing internal valve that only opens during operating periods. The mechanism for such valves may have a secondary control that will close automatically in case of fire. The melting point for a fusible plug must be a maximum of 220°F.

(2) A filling pipe inlet terminal off the container must have a positive shut-off valve and either:
(a) A back pressure check valve; or
(b) An excess flow check valve.
(3) All openings in the container must have approved

Exceptions:

(a)Filling connections;

(b)Safety-relief connections;

(c)Liquid-level gauging devices; and

(d)Pressure gauge connections.

(4) All container inlets and outlets must be labeled to designate whether they connect with vapor or liquid (labels may be on valves).

Exceptions:

(a)Safety-relief valves;

(b)Liquid-level gauging devices; and

(c)Pressure gauges.

(5) Each storage container must have a suitable pressure gauge.

Wash. Admin. Code § 296-307-44005

Amended by WSR 20-21-091, Filed 10/20/2020, effective 11/20/2020

97-09-013, recodified as § 296-307-44005, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040,[49.17.]050 and [49.17.]060. 96-22-048, § 296-306A-44005, filed 10/31/96, effective 12/1/96.