Wash. Admin. Code § 296-307-42509

Current through Register Vol. 24-23, December 1, 2024
Section 296-307-42509 - Valves and accessories
(1) Container valves and accessories must have a rated working pressure of at least 250 psig, and must be suitable for LP-gas service.
(2) The filling connection must be fitted with an approved double back-pressure check valve, or a positive shutoff in conjunction with an internal back-pressure check valve. On a removable container the filler valve may be a hand operated shut-off valve with an internal excess flow valve. Main shut-off valves on the container on liquid and vapor must be readily accessible.
(3) Filling connections equipped with approved automatic back-pressure check valves, and safety-relief valves, all connections to the containers having openings for the flow of gas in excess of a No. 54 drill size must have approved automatic excess flow valves to prevent discharge of content in case connections are broken.
(4) Liquid-level gauging devices must meet the following requirements:
(a) Variable liquid-level gauges that require the venting of fuel to the atmosphere are prohibited on fuel containers of industrial trucks (including lift trucks).
(b) On portable containers that may be filled in the vertical and/or horizontal position, the fixed liquid-level gauge must indicate maximum permitted filling level for both vertical and horizontal filling with the container oriented to place the safety-relief valve in communication with the vapor space.
(c) For containers used solely in farm tractor service and charged at a point at least 50 feet from any important building, the fixed liquid-level gauging device may be constructed so that the outward flow of container content exceeds that passed by a No. 54 drill size opening, but must never exceed that passed by a No. 31 drill-size opening. An excess flow valve is not required. Fittings equipped with restricted drill size opening and the container on which they are used must be marked to indicate the size of the opening.
(d) All valves and connections on containers must be adequately protected to prevent damage due to accidental contact with stationary objects or from loose objects thrown up from the road. All valves must be safeguarded against damage due to collision, overturning or other accident. Farm tractors where parts of the vehicle provide protection to valves and fittings meet this requirement. However, on removable type containers the protection for the fittings must be permanently attached to the container.
(e) The employer should normally exchange removable fuel outdoors. When removable fuel containers are used, means must be provided in the fuel system to minimize the escape of fuel when the containers are exchanged. The employer must use one of the following methods:
(i) Using an approved automatic quick-closing coupling (a type closing in both directions when uncoupled) in the fuel line; or
(ii) Closing the valve at the fuel container and allowing the engine to run until the fuel in the line is consumed.

Wash. Admin. Code § 296-307-42509

Amended by WSR 20-21-091, Filed 10/20/2020, effective 11/20/2020

97-09-013, recodified as § 296-307-42509, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040,[49.17.]050 and [49.17.]060. 96-22-048, § 296-306A-42509, filed 10/31/96, effective 12/1/96.