TABLE U-7
Regulator delivery pressure | Relief valve start-to-discharge pressure setting (percent of regulator delivery pressure) | |
Minimum | Maximum | |
1 psig or less | 200 | 300 |
Above 1 psig but not over 3 psig | 140 | 200 |
Above 3 psig | 125 | 200 |
Exception: | This requirement does not apply to individual appliance regulators when protection is otherwise provided, nor to WAC 296-307-41509 and 296-307-41025(14). In buildings devoted exclusively to gas distribution, the space above the diaphragm need not be vented to the outside. |
Wash. Admin. Code § 296-307-41513
Statutory Authority: RCW 49.17.040. 98-24-096, § 296-307-41513, filed 12/1/98, effective 3/1/99. 97-09-013, recodified as § 296-307-41513, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. 96-22-048, § 296-306A-41513, filed 10/31/96, effective 12/1/96.