Section 296-307-41513 - Safety devices for cylinder systems
(1) Containers must have safety devices as required by DOT regulations.
(2) A final stage regulator of an LP-gas system (excluding any appliance regulator) must have, on the low-pressure side, a relief valve that is set to start to discharge within the limits specified in Table U-7.

TABLE U-7

Regulator delivery pressureRelief valve start-to-discharge pressure setting (percent of regulator delivery pressure)
MinimumMaximum
1 psig or less 200 300
Above 1 psig but not over 3 psig 140 200
Above 3 psig 125 200

(3) When a regulator or pressure relief valve is used indoors for other than purposes specified in WAC 296-307-41017(1), the relief valve and the space above the regulator and relief valve diaphragms must be vented to the outside air with the discharge outlet located at least three feet horizontally away from any building opening that is below such discharge.

Exception: This requirement does not apply to individual appliance regulators when protection is otherwise provided, nor to WAC 296-307-41509 and 296-307-41025(14). In buildings devoted exclusively to gas distribution, the space above the diaphragm need not be vented to the outside.

Wash. Admin. Code § 296-307-41513

Amended by WSR 20-21-091, Filed 10/20/2020, effective 11/20/2020

Statutory Authority: RCW 49.17.040. 98-24-096, § 296-307-41513, filed 12/1/98, effective 3/1/99. 97-09-013, recodified as § 296-307-41513, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040, [49.17.]050 and [49.17.]060. 96-22-048, § 296-306A-41513, filed 10/31/96, effective 12/1/96.