Section 296-307-40017 - Locations for anhydrous ammonia containers
(1) When selecting the location for a storage container, the employer must take into account the physiological effects of ammonia and adjacent fire hazards. Containers located indoors must be in areas especially approved for container storage.
(2) Containers must be located at least fifty feet from a dug well or other sources of potable water supply, unless the container is a part of a water treatment installation.
(3) Permanent storage containers must be located outside densely populated areas.
(4) Containers must be located according to the following:

Minimum distances (feet) from container to:

Nominal capacity of container

Line of adjoining property that may be built upon, highways & main line of railroad

Place of public

Institution assembly occupancy

Over 500 to 2,000

25

150

250

Over 2,000 to 30,000

50

300

500

Over 30,000 to 100,000

50

450

750

Over 100,000

50

600

1,000

(5) Storage areas must be kept free of readily ignitable materials such as waste, weeds and long dry grass.