Wash. Admin. Code § 296-307-36603

Current through Register Vol. 24-23, December 1, 2024
Section 296-307-36603 - Use and identification of grounded and grounding conductors
(1) A conductor used as a grounded conductor must be identified separately from all other conductors. A conductor used as an equipment grounding conductor must be identified separately from all other conductors.
(2) A grounded conductor must not be attached to any terminal or lead to reverse the designated polarity.
(3) Using a grounding terminal or grounding-type device on a receptacle, cord connector, or attachment plug for anything other than grounding is prohibited.

Wash. Admin. Code § 296-307-36603

Amended by WSR 20-21-091, Filed 10/20/2020, effective 11/20/2020

97-09-013, recodified as § 296-307-36603, filed 4/7/97, effective 4/7/97. Statutory Authority: RCW 49.17.040,[49.17.]050 and [49.17.]060. 96-22-048, § 296-306A-36603, filed 10/31/96, effective 12/1/96.