Current through Register Vol. 24-23, December 1, 2024
Section 296-150T-0350 - What must the test procedures and results for design plans include?(1) Tests to a design for a factory-built temporary worker housing structure must be witnessed by a professional engineer or architect licensed in Washington state.(2) Test reports must contain the following items:(a) A description of the methods or standards that applied to the test;(b) Drawings and a description of the item tested;(c) A description of the test set-up;(d) The procedure used to verify the correct load;(e) The procedure used to measure each condition;(f) Test data, including applicable graphs and observations of the characteristics and behavior of the item tested; and(g) Analysis, comments, and conclusion.(3) The written test procedures, results and conclusions must reference the applicable design plan.Wash. Admin. Code § 296-150T-0350
Statutory Authority: RCW 43.22.480. 99-12-079, § 296-150T-0350, filed 5/28/99, effective 6/28/99.