Section 246-359-170 - Wood framed construction and concrete masonry unit (CMU) general limitations(1) When building with wood or CMU as required by WAC 246-359-200 through 246-359-580 the following requirements apply:(a) Floor area must be limited to three thousand six hundred square feet per building;(b) Height must be limited to one story; and(c) All floor surfaces must be above grade, no basements.(2) When building to WAC 246-359-600, alternate construction, the limitations in subsection (1) of this section do not apply.Wash. Admin. Code § 246-359-170
Statutory Authority: RCW 70.114A.081. 99-03-065, § 246-359-170, filed 1/18/99, effective 2/18/99.