Owners and operators must ensure site assessments, including site checks, are performed in accordance with the requirements of this section.
Table 0730-1: Minimum Number and Location of Soil Samples
Tanks | Piping | Dispensers | |
In Place | Collect the following samples around the excavation zone where contamination is most likely to be present: | Collect one sample for every 50 feet of piping. For example, collect one sample if the piping run is less than 50 feet and two samples if the piping run is 50 to 100 feet. Collect the samples adjacent to the piping where contamination is most likely to be present, such as at connections, fittings, or elbows. (1, 2) | Collect one sample adjacent to each dispenser.(1, 2) |
* When assessing single tank with a capacity of < 9,000 gallons, collect three samples, one at each end and one on another side of the tank. (1, 2) | |||
* When assessing single tank with a capacity of [GREATER THAN EQUAL TO] 9,000 gallons, collect four samples, one at each side of the tank.(1, 2) | |||
* When assessing multiple tanks in an excavation zone, collect four samples for the first tank and two additional samples for each additional tank, spacing the samples evenly around the excavation zone. (1, 2) | |||
Removed | Collect the following samples within the excavation zone where contamination is most likely to be present: | Collect one sample for every 50 feet of piping. For example, collect one sample if the piping run is less than 50 feet and two samples if the piping run is 50 to 100 feet. Collect the samples beneath the piping where contamination is most likely to be present, such as at connections, fittings, or elbows. (2) | Collect one sample beneath each dispenser. (2) |
* When assessing single tank with a capacity of < 9,000 gallons, collect three samples, one beneath the tank (2), one beneath where the piping from the tank entered a sidewall, and one from another sidewall. | |||
* When assessing single tank with a capacity of [GREATER THAN EQUAL TO] 9,000 gallons, collect five samples, one from beneath the tank (2), one beneath where the piping from the tank entered a sidewall, and one from each of the other three sidewalls. | |||
* When assessing multiple tanks from an excavation zone, collect five samples for the first tank and two additional samples for each additional tank, one beneath each tank (2), one beneath where piping from each tank entered a sidewall, and spacing remaining samples evenly around the sidewalls. | |||
Collect the following samples from excavated soils where contamination is most likely to be present: | |||
Cubic Yards of Soil | Minimum Number of Samples | ||
0-25 | 1 | ||
26-50 | 2 | ||
51-100 | 3 | ||
101-500 | 5 | ||
501-1000 | 7 | ||
1001-2000 | 10 | ||
>2000 | 10 + 1 additional sample for each additional 500 cubic yards of soil |
Footnotes: | (1) Horizontal distance: The specified samples must be collected from native soil as close as practicable to, but no more than ten feet from the applicable tank, pipe, or dispenser. |
(2) Vertical distance: The specified samples must be collected from native soil as close as practicable to the bottom of the applicable tank, pipe, or dispenser. If groundwater is encountered, soil samples must be collected at the approximate top of the water table. |
Wash. Admin. Code § 173-360A-0730
Statutory Authority: Chapter 90.76 RCW. WSR 18-15-083 (Order 16-02), § 173-360A-0730, filed 7/18/18, effective 10/1/18.