Table III Emissions Limits for CI Units Located in Attainment Areas | ||||||||
Generator Size (kW) | Displacement liters/cylinder | Model Year | Emission Limits g/kW-hr (g/bhp-hr) | |||||
PM | PM10 | PM2.5 | CO | VOC | NOx | |||
x < 8 kW | Less than 10 | 2010+ | 0.4 | 0.4 | 0.4 | 8.0 | 7.5* | |
(x < 11 bhp) | (0.30) | (0.30) | (0.30) | (6.0) | (5.6*) | |||
8 kW <= x < 19 kW | Less than 10 | 2010+ | 0.4 | 0.4 | 0.4 | 6.6 | 7.5* | |
(11 bhp <= x < 25 bhp) | (0.30) | (0.30) | (0.30) | (4.9) | (5.6*) | |||
19 kW <= x < 37 kW | Less than 10 | 2010+ | 0.3 | 0.3 | 0.3 | 5.5 | 7.5* | |
(25 bhp <= x < 50 bhp) | (0.22) | (0.22) | (0.22) | (4.1) | (5.6*) | |||
37 kW <= x < 75 kW | Less than 10 | 2010+ | 0.4 | 0.4 | 0.4 | 5.0 | 4.7* | |
(50 bhp <= x < 100 bhp) | (0.30) | (0.30) | (0.30) | (3.7) | (3.5*) | |||
75 kW <= x < 130 kW | Less than 10 | 2010+ | 0.3 | 0.3 | 0.3 | 5.0 | 4.0* | |
(100 bhp <= x < 174 bhp) | (0.22) | (0.22) | (0.22) | (3.7) | (3.0*) | |||
130 kW <= x < 560 kW | Less than 10 | 2010+ | 0.2 | 0.2 | 0.2 | 3.5 | 4.0* | |
(174 bhp <= x < 751 bhp) | (0.15) | (0.15) | (0.15) | (2.6) | (3.0*) | |||
560 kW <= x < 2,237 kW | Less than 10 | 2010+ | 0.2 | 0.2 | 0.2 | 3.5 | 6.4* | |
(751 bhp <= x < 3,000 bhp) | (0.15) | (0.15) | (0.15) | (2.6) | (4.8*) | |||
x [GREATER THAN EQUALS TO] 2,237 kW | Less than 10 | 2010 | 0.54 | 0.54 | 0.54 | 11.4 | 1.3 | 9.2 |
(x [GREATER THAN EQUALS TO] 3,000 bhp) | (0.40) | (0.40) | (0.40) | (8.5) | (1.0) | (6.9) | ||
2011+ | 0.2 | 0.2 | 0.2 | 3.5 | 6.4* | |||
(0.15) | (0.15) | (0.15) | (2.6) | (4.8*) | ||||
x [GREATER THAN EQUALS TO] 2,237 kW | 10.0 <= x < 15.0 | 2010+ | 0.27 | 0.27 | 0.27 | 5.0 | 7.8* | |
(x [GREATER THAN EQUALS TO] 3,000 bhp) | (0.20) | (0.20) | (0.20) | (3.7) | (5.8*) | |||
*Combined limit for VOC and NOx |
Table IV Emissions Limits for CI Units Located in Attainment Areas | ||||||||
Generator Size (kW) | Displacement liters/cylinder | Model Year | Emission Limits (g/kW-hr (g/bhp-hr) | |||||
PM | PM10 | PM2.5 | CO | VOC | NOx | |||
x < 8 kW | Less than 10 | 2010+ | 0.5 | 0.5 | 0.5 | 10.0 | 9.4* | |
(x < 11 bhp) | (0.4) | (0.4) | (0.4) | (7.5) | (7.0*) | |||
8 kW <= x < 19 kW | Less than 10 | 2010+ | 0.5 | 0.5 | 0.5 | 8.3 | 9.4* | |
(11 bhp <= x < 25 bhp) | (0.4) | (0.4) | (0.4) | (6.2) | (7.0*) | |||
19 kW <= x < 37 kW | Less than 10 | 2010+ | 0.38 | 0.38 | 0.38 | 6.9 | 9.4* | |
(25 bhp <= x < 50 bhp) | (0.28) | (0.28) | (0.28) | (5.1) | (7.0*) | |||
37 kW <= x < 75 kW | Less than 10 | 2010+ | 0.5 | 0.5 | 0.5 | 6.3 | 5.9* | |
(50 bhp <= x < 100 bhp) | (0.4) | (0.4) | (0.4) | (4.7) | (4.4*) | |||
75 kW <= x < 130 kW | Less than 10 | 2010+ | 0.38 | 0.38 | 0.38 | 6.3 | 5.0* | |
(100 bhp <= x < 174 bhp) | (0.28) | (0.28) | (0.28) | (4.7) | (3.7*) | |||
130 kW <= x < 560 kW | Less than 10 | 2010+ | 0.25 | 0.25 | 0.25 | 4.4 | 5.0* | |
(174 bhp <= x < 751 bhp) | (0.19) | (0.19) | (0.19) | (3.3) | (3.7*) | |||
560 kW <= x < 2,237 kW | Less than 10 | 2010+ | 0.25 | 0.25 | 0.25 | 4.4 | 8.0* | |
(751 bhp <= x < 3,000 bhp) | (0.19) | (0.19) | (0.19) | (3.3) | (6.0*) | |||
x [GREATER THAN EQUALS TO] 2,237 kW | Less than 10 | 2010 | 0.68 | 0.68 | 0.68 | 14.3 | 1.6 | 11.5 |
(x [GREATER THAN EQUALS TO] 3,000 bhp) | (0.51) | (0.51) | (0.51) | (10.7) | (1.2) | (8.6) | ||
2011+ | 0.25 | 0.25 | 0.25 | 4.4 | 8.0* | |||
(0.19) | (0.19) | (0.19) | (3.3) | (6.0*) | ||||
x [GREATER THAN EQUALS TO] 2,237 kW | 10.0 <= x < 15.0 | 2010+ | 0.34 | 0.34 | 0.34 | 6.3 | 9.8* | |
(x [GREATER THAN EQUALS TO] 3,000 bhp) | (0.25) | (0.25) | (0.25) | (4.7) | (7.3*) | |||
*Combined limit for VOC and NOx |
Table V Emissions Limits for CI Units Located in Nonattainment Areas | ||||||||
Generator Size (kW) | Displacement liters/cylinder | Model Year | Emission Limits g/kW-hr (g/bhp-hr) | |||||
PM | PM10 | PM2.5 | CO | VOC | NOx | |||
x < 8 kW | Less than 10 | 2010+ | 0.4 | 0.4 | 0.4 | 8.0 | 6.4* | |
(x < 11 bhp) | (0.30) | (0.30) | (0.30) | (6.0) | (4.8*) | |||
8 kW <= x < 19 kW | Less than 10 | 2010+ | 0.4 | 0.4 | 0.4 | 6.6 | 6.4* | |
(11 bhp <= x < 25 bhp) | (0.30) | (0.30) | (0.30) | (4.9) | (4.8*) | |||
19 kW <= x < 37 kW | Less than 10 | 2010+ | 0.3 | 0.3 | 0.3 | 5.5 | 6.4* | |
(25 bhp <= x < 50 bhp) | (0.22) | (0.22) | (0.22) | (4.1) | (4.8*) | |||
37 kW <= x < 75 kW | Less than 10 | 2010+ | 0.4 | 0.4 | 0.4 | 5.0 | 4.7* | |
(50 bhp <= x < 100 bhp) | (0.30) | (0.30) | (0.30) | (3.7) | (3.5*) | |||
75 kW <= x < 130 kW | Less than 10 | 2010+ | 0.3 | 0.3 | 0.3 | 5.0 | 4.0* | |
(100 bhp <= x < 174 bhp) | (0.22) | (0.22) | (0.22) | (3.7) | (3.0*) | |||
130 kW <= x < 560 kW | Less than 10 | 2010+ | 0.2 | 0.2 | 0.2 | 3.5 | 4.0* | |
(174 bhp <= x < 751 bhp) | (0.15) | (0.15) | (0.15) | (2.6) | (3.0*) | |||
560 kW <= x < 2,237 kW | Less than 10 | 2010+ | 0.2 | 0.2 | 0.2 | 3.5 | 6.4* | |
(751 bhp <= x < 3,000 bhp) | (0.15) | (0.15) | (0.15) | (2.6) | (4.8*) | |||
x [GREATER THAN EQUALS TO] 2,237 kW | Less than 10 | 2010 | 0.54 | 0.54 | 0.54 | 11.4 | 1.3 | 6.4 |
(x [GREATER THAN EQUALS TO] 3,000 bhp) | (0.40) | (0.40) | (0.40) | (8.5) | (1.0) | (4.8) | ||
2011+ | 0.2 | 0.2 | 0.2 | 3.5 | 6.4* | |||
(0.15) | (0.15) | (0.15) | (2.6) | (4.8*) | ||||
x [GREATER THAN EQUALS TO] 2,237 kW | 10.0 <= x < 15.0 | 2010+ | 0.27 | 0.27 | 0.27 | 5.0 | 6.4* | |
(x [GREATER THAN EQUALS TO] 3,000 bhp) | (0.20) | (0.20) | (0.20) | (3.7) | (4.8*) | |||
*Combined limit for VOC and NOx |
Table VI Emissions Limits During Testing for CI Units Located in Nonattainment Areas | ||||||||
Generator Size (kW) | Displacement liters/cylinder | Model Year | Emission Limits g/kW-hr (g/bhp-hr) | |||||
PM | PM10 | PM2.5 | CO | VOC | NOx | |||
x < 8 kW | Less than 10 | 2010+ | 0.5 | 0.5 | 0.5 | 10.0 | 8.0* | |
(x < 11 bhp) | (0.4) | (0.4) | (0.4) | (7.5) | (6.0*) | |||
8 kW <= x < 19 kW | Less than 10 | 2010+ | 0.5 | 0.5 | 0.5 | 8.3 | 8.0* | |
(11 bhp <= x < 25 bhp) | (0.4) | (0.4) | (0.4) | (6.2) | (6.0*) | |||
19 kW <= x < 37 kW | Less than 10 | 2010+ | 0.38 | 0.38 | 0.38 | 6.9 | 8.0* | |
(25 bhp <= x < 50 bhp) | (0.28) | (0.28) | (0.28) | (5.1) | (6.0*) | |||
37 kW <= x < 75 kW | Less than 10 | 2010+ | 0.5 | 0.5 | 0.5 | 6.3 | 5.9* | |
(50 bhp <= x < 100 bhp) | (0.4) | (0.4) | (0.4) | (4.7) | (4.4*) | |||
75 kW <= x < 130 kW | Less than 10 | 2010+ | 0.38 | 0.38 | 0.38 | 6.3 | 5.0* | |
(100 bhp <= x < 174 bhp) | (0.28) | (0.28) | (0.28) | (4.7) | (3.7*) | |||
130 kW <= x < 560 kW | Less than 10 | 2010+ | 0.25 | 0.25 | 0.25 | 4.4 | 5.0* | |
(174 bhp <= x < 751 bhp) | (0.19) | (0.19) | (0.19) | (3.3) | (3.7*) | |||
560 kW <= x < 2,237 kW | Less than 10 | 2010+ | 0.25 | 0.25 | 0.25 | 4.4 | 8.0* | |
(751 bhp <= x < 3,000 bhp) | (0.19) | (0.19) | (0.19) | (3.3) | (6.0*) | |||
x [GREATER THAN EQUALS TO] 2,237 kW | Less than 10 | 2010 | 0.68 | 0.68 | 0.68 | 14.3 | 1.6 | 8.0 |
(x [GREATER THAN EQUALS TO] 3,000 bhp) | (0.51) | (0.51) | (0.51) | (10.7) | (1.2) | (6.0) | ||
2011+ | 0.25 | 0.25 | 0.25 | 4.4 | 8.0* | |||
(0.19) | (0.19) | (0.19) | (3.3) | (6.0*) | ||||
x [GREATER THAN EQUALS TO] 2,237 kW | 10.0 <= x < 15.0 | 2010+ | 0.34 | 0.34 | 0.34 | 6.3 | 8.0* | |
(x [GREATER THAN EQUALS TO] 3,000 bhp) | (0.25) | (0.25) | (0.25) | (4.7) | (6.0*) | |||
*Combined limit for VOC and NOx |
Table VII Emissions Limits for SI Units | ||||||
Model Year | Emissions Limits g/kW-hr (g/bhp-hr) | |||||
PM | PM10 | PM2.5 | CO | VOC | NOx | |
2010+ | 0.015 | 0.015 | 0.015 | 5.3 | 1.3 | 2.7 |
(0.011) | (0.011) | (0.011) | (4.0) | (1.0) | (2.0) | |
Instead of meeting the limits stated above, the owner may meet the alternative standards below: ( ppmvd at 15% O2) | ||||||
540 | 86 | 160 |
Table VIII Combined Source-Wide Emissions Limits for Affected Units | ||
Pollutant | Nonattainment Area Emissions (tons/year) | Attainment Area Emissions (tons/year) |
PM | 1.4 | 2.3 |
PM10 | 1.4 | 2.3 |
PM2.5 | 1.4 | 2.3 |
NOX | 24.4 | 39.4 |
SO2 | 0.5 | 0.5 |
CO | 48.0 | 77.4 |
VOC | 11.8 | 19.0 |
9 Va. Admin. Code § 5-540-180
Statutory Authority
§§ 10.1-1307.2 and 10.1-1308 of the Code of Virginia.