Note: The following codes of practice may be used to comply with subsection B of this section:
Maximum Leak Detection Rate Per Test Section Volume | ||
Test Section Volume (Gallons) | Semiannual Test - Leak Detection Rate Not To Exceed (Gallons Per Hour) | Annual Test - Leak Detection Rate Not To Exceed (Gallons Per Hour) |
< 50,000 | 1.0 | 0.5 |
>= 50,000 to < 75,000 | 1.5 | 0.75 |
>= 75,000 to < 100,000 | 2.0 | 1.0 |
>= 100,000 | 3.0 | 1.5 |
Phase in for Piping Segments >= 100,000 Gallons in Volume | |
First test | Not later than January 1, 2021, (may use up to 6.0 gph leak rate) |
Second test | Between January 1, 2021, and January 1, 2024, (may use up to 6.0 gph leak rate) |
Third test | Between January 1, 2024, and January 1, 2025, (must use 3.0 gph for leak rate) |
Subsequent tests | After January 1, 2025, begin using semiannual or annual line testing according to the Maximum Leak Detection Rate Per Test Section Volume table above |
9 Va. Admin. Code § 25-580-390
Statutory Authority: §§ 62.1-44.15 and 62.1-44.34:9 of the Code of Virginia; 42 USC § 6901 et seq.; 40 CFR Parts 280 and 281.