Section 9VAC25-580-140 - Requirements for petroleum UST systems Owners and operators of petroleum UST systems must provide release detection for tanks and piping as follows:
1. Tanks. Tanks must be monitored for releases as follows:a. Tanks installed before September 15, 2010, must be monitored for releases at least every 30 days for releases using one of the methods listed in subdivisions 4 through 9 of 9VAC25-580-160 except that: (1) UST systems that meet the performance standards in subdivisions 1 through 5 of 9VAC25-580-50 or subdivisions 1 through 4 of 9VAC25-580-60 may use both monthly inventory control requirements in subdivision 1 or 2 of 9VAC25-580-160, and tank tightness testing (conducted in accordance with subdivision 3 of 9VAC25-580-160) at least every five years until 10 years after the tank was installed; and(2) Tanks with capacity of 550 gallons or less and tanks with a capacity of 551 to 1000 gallons that meet the tank diameter criteria in subdivision 2 of 9VAC25-580-160 may use manual tank gauging (conducted in accordance with subdivision 2 of 9VAC25-580-160) .b. Tanks installed on or after September 15, 2010, must be monitored for releases at least every 30 days in accordance with subdivision 7 of 9VAC25-580-160.2. Piping. Underground piping that routinely contains regulated substances must be monitored for releases in a manner that meets one of the following requirements: a. Piping installed before September 15, 2010, must meet one of the following: (1) Pressurized piping. Underground piping that conveys regulated substances under pressure must: (a) Be equipped with an automatic line leak detector conducted in accordance with subdivision 1 of 9VAC25-580-170; and(b) Have an annual line tightness test conducted in accordance with subdivision 2 of 9VAC25-580-170 or have monthly monitoring conducted in accordance with subdivision 3 of 9VAC25-580-170.(2) Suction piping. Underground piping that conveys regulated substances under suction must either have a line tightness test conducted at least every three years and in accordance with subdivision 2 of 9VAC25-580-170, or use a monthly monitoring method conducted in accordance with subdivision 3 of 9VAC25-580-170. No release detection is required for suction piping that is designed and constructed to meet the following standards: (a) The below-grade piping operates at less than atmospheric pressure;(b) The below-grade piping is sloped so that the contents of the pipe will drain back into the storage tank if the suction is released;(c) Only one check valve is included in each suction line;(d) The check valve is located directly below and as close as practical to the suction pump; and(e) A method is provided that allows compliance with subdivisions 2 a (2) (b), (c), and (d) of this subsection to be readily determined.b. Piping installed or replaced on or after September 15, 2010, must meet one of the following: (1) Pressurized piping must be monitored for releases at least every 30 days in accordance with subdivision 7 of 9VAC25-580-160 and be equipped with an automatic line leak detector in accordance with subdivision 1 of 9VAC25-580-170.(2) Suction piping must be monitored for releases at least every 30 days in accordance with subdivision 7 of 9VAC25-580-160. No release detection is required for suction piping that meets the requirements of subdivisions 2 a (2) (a) through (e) of this section.9 Va. Admin. Code § 25-580-140
Derived from VR680-13-02 §4.2, eff. October 25, 1989; amended, Volume 26, Issue 25, eff. September 15, 2010; Amended, Virginia Register Volume 34, Issue 01, eff. 1/1/2018; Errata, 34:4 VA.R. 503 October 16, 2017.Statutory Authority: §§ 62-1.44.15 and 62.1-44.34:9 of the Code of Virginia; 42 USC § 6901 et seq.; 40 CFR "part"s 280 and 281.