Current through Register Vol. 41, No. 8, December 2, 2024
Section 6VAC15-81-1030 - Fire protectionA. Sprinkler heads in inmate accessible areas shall be detention type heads.B. Exposed fire alarms, smoke detectors, heat detectors, and audible and visual signaling devices shall be mounted as high as practicable, and if below 12 feet, they shall be covered with heavy-gage tamper-resistant protective cages securely fastened to the surface. All exposed devices including sprinkler heads in gymnasiums or indoor recreation areas shall be covered with protective cages.6 Va. Admin. Code § 15-81-1030
Derived From Virginia Register Volume 34, Issue 12, eff. 3/8/2018.Statutory Authority: 53.1-5, 53.1-80, and 53.1-82 of the Code of Virginia.