6 Va. Admin. Code § 15-81-880

Current through Register Vol. 41, No. 8, December 2, 2024
Section 6VAC15-81-880 - Mechanical, maintenance, security electronics
A. The main mechanical room shall be located outside the secure perimeter and shall be accessible from the outside.
B. If a separate maintenance shop is provided, it shall be located outside the secure perimeter and shall be accessible from the outside.
C. The main security electronics shall be contained in a room specifically designed for that purpose or shall be securely separated from other equipment. Security electronic rooms shall not provide access to other spaces or services. An independent cooling system shall be provided for this room.

6 Va. Admin. Code § 15-81-880

Derived From Virginia Register Volume 34, Issue 12, eff. 3/8/2018.

Statutory Authority: 53.1-5, 53.1-80, and 53.1-82 of the Code of Virginia.