VT = Tornado speed, miles per hour (mph) (m/s) determined from Chapter 32 of ASCE 7.
In nonhurricane-prone regions, when the basic design wind speed, V, is estimated from regional climatic data, the basic design wind speed, V, shall be determined in accordance with Section 26.5.3 of ASCE 7.
EDITOR'S NOTE: Figure 1609.5 Tornado-Prone Region has not been amended since being published in the proposed regulation in 39:14 VA.R. 1856-2028 February 27, 2023; therefore Figure 1609.5 is not set out.
Exception: Rigid tile roof coverings that are air permeable and installed over a roof deck complying with Section 1609.6.1 are permitted to be designed in accordance with Section 1609.6.3.
Asphalt shingles installed over a roof deck complying with Section 1609.6.1 shall comply with the wind-resistance requirements of Section 1504.2.
(Equation 16-18)
For SI:
where:b = Exposed width, feet (mm) of the roof tile.
CL = Lift coefficient. The lift coefficient for concrete and clay tile shall be 0.2 or shall be determined by test in accordance with Section 1504.3.1.
GCp = Roof pressure coefficient for each applicable roof zone determined from Chapter 30 of ASCE 7. Roof coefficients shall not be adjusted for internal pressure.
L = Length, feet (mm) of the roof tile.
La = Moment arm, feet (mm) from the axis of rotation to the point of uplift on the roof tile. The point of uplift shall be taken at 0.76L from the head of the tile and the middle of the exposed width. For roof tiles with nails or screws (with or without a tail clip), the axis of rotation shall be taken as the head of the tile for direct deck application or as the top edge of the batten for battened applications. For roof tiles fastened only by a nail or screw along the side of the tile, the axis of rotation shall be determined by testing. For roof tiles installed with battens and fastened only by a clip near the tail of the tile, the moment arm shall be determined about the top edge of the batten with consideration given for the point of rotation of the tiles based on straight bond or broken bond and the tile profile.
Ma = Aerodynamic uplift moment, feet-pounds (N-mm) acting to raise the tail of the tile.
qh = Wind velocity pressure, psf (kN/m2 ) determined from Section 26.10.2 of ASCE 7.
Concrete and clay roof tiles complying with the following limitations shall be designed to withstand the aerodynamic uplift moment as determined bythis section.
qhT = tornado velocity pressure, psf (kN/m2 ) determined in accordance with Section 32.10 of ASCE 7.
KvT = tornado pressure coefficient adjustment factor for vertical winds, determined in accordance with Section 32.14 of ASCE 7.
Exception: Manufactured homes installed on sites in an existing manufactured home park or subdivision shall be permitted to be placed so that the manufactured home chassis is supported by reinforced piers or other foundation elements of at least equivalent strength that are no less than 36 inches (914 mm) above grade in lieu of being elevated at or above the base flood elevation, provided no manufactured home at the same site has sustained flood damage exceeding 50% of the market value of the home before the damage occurred.
13 Va. Admin. Code § 5-63-270
Statutory Authority: § 36-98 of the Code of Virginia.