Section R309-545-9 - Tank Roof and Sidewalls
(1) Protection From Contamination.

All drinking water storage tanks shall have suitable watertight roofs and sidewalls that shall also exclude birds, animals, insects, and excessive dust.

(2) Openings.

Openings in the roof and sidewalls shall be kept to a minimum and shall comply with the following:

(a) Any pipes running through the roof or sidewall of a metal drinking water storage tank shall be welded, or properly gasketed. In new concrete tanks, these pipes shall be connected to standard wall castings with seepage rings that have been poured in place. Vent pipes, in addition to seepage rings, shall have raised concrete curbs that direct water away from the vent pipe and are formed as a single pour with the roof deck. Roof drains or any other pipes, which may contain water of lesser quality than drinking water, shall not penetrate the roof, walls, or floor of a drinking water storage tank.
(b) Openings in a storage tank roof or top, designated to accommodate control apparatus or pump columns, shall be welded, gasketed, or curbed and sleeved as above, and shall have additional proper shielding to prevent vandalism.
(3) Adjacent Compartments.

Drinking water shall not be stored or conveyed in a compartment adjacent to wastewater when the two compartments are separated by a single wall.

(4) Roof Drainage.

The roof of all storage tanks shall be designed for drainage to eliminate water ponding. Parapets, or similar structures, which would tend to hold water and snow, shall not be allowed/permitted unless adequate waterproofing and drainage are provided. Downspout or roof drain pipes shall not enter or pass through the tank.

Utah Admin. Code R309-545-9