Current through Bulletin 2024-23, December 1, 2024
Section R309-510-4 - General(1) This rule provides minimum quantities and flow rates that shall be used in the design of new systems and in the evaluation of water source, storage facility, and pipeline capacities, unless a public water system has obtained a capacity reduction per R309-510-5. Water demand may vary significantly depending on water system size, type, land use, urbanization, location, precipitation, etc. Therefore, public water systems may submit system-specific water use data to justify alternative sizing requirements in accordance with R309-510-5.(2) When designing a public water system, the sizing requirements for indoor water use, irrigation, and fire suppression (as required by the local fire code official) shall be included as appropriate.(3) Local authorities may impose more stringent design requirements on public water systems than the minimum sizing requirements of this rule.(4) Public water systems shall consider daily, weekly, monthly, seasonal, and yearly variations of source capacity and system demand and shall verify that the capacities of drinking water facilities are sufficiently sized.(5) The Director may modify the sizing requirements based on the unique nature and use of a water system.Utah Admin. Code R309-510-4
Amended by Utah State Bulletin Number 2015-15, effective 7/15/2015