Current through Bulletin 2024-23, December 1, 2024
Section R309-230-7 - Permanent Control MeasuresFollowing receipt of results that show a consumable tap has five or more parts per billion of lead, a school or child care center shall:
(1) Implement one of the following permanent control measures:(a) Replacement of the consumable tap with a replacement faucet that has been third-party certified to NSF or ANSI standard 372 for lead-free compliance and NSF or ANSI standard 61 for material safety.(b) Installation of a water treatment device at the tap. The water treatment device must be certified to capture lead according to NSF or ANSI standard 53 or NSF or ANSI standard 58. Schools shall follow the manufacturer's instructions for installation, use, and maintenance. For each water treatment device installed, schools shall create a maintenance schedule that identifies a point of contact to oversee making sure they are properly installed and maintained.(c) Permanently shut off and remove the consumable tap.(2) If control measures stated in Subsection (1)(a) or (1)(b) are completed, the school or child care center shall take a follow-up sample of the consumable tap and have those samples evaluated by a certified laboratory to demonstrate that lead is less than five parts per billion before access to the tap is resumed. Each sample taken must comply with requirements in Section R309-230-5.(3) A school or child care center may apply for reimbursement for costs associated with permanent control measures for consumable taps with the Division of Drinking Water.Utah Admin. Code R309-230-7
Adopted by Utah State Bulletin Number 2022-22, effective 11/1/2022