Utah Admin. Code 309-211-5

Current through Bulletin 2024-23, December 1, 2024
Section R309-211-5 - Routine Monitoring Requirements for Water Systems Serving 1,000 or Fewer People
(1) General.
(a) The provisions of this section apply to water systems serving 1,000 or fewer people.
(b) Following any total coliform-positive sample taken under the provisions of this section, systems must comply with the repeat monitoring requirements and E. coli analytical requirements in R309-211-7.
(c) Once all monitoring required by this section and R309-211-7 for a calendar month has been completed, systems must determine whether any coliform treatment technique triggers specified in R309-211-8 have been exceeded. If any trigger has been exceeded, systems must complete assessments as required by R309-211-8.
(2) Monitoring frequency for total coliforms. The monitoring frequency for total coliforms is one sample/month.
(3) Seasonal systems.
(a) All seasonal systems must demonstrate completion of a Director-approved start-up procedure, which may include a requirement for startup sampling prior to serving water to the public.
(b) A seasonal system must monitor every month that it is in operation.
(c) The Director may exempt any seasonal system from some or all of the requirements for seasonal systems if the entire distribution system remains pressurized during the entire period that the system is not operating.

Utah Admin. Code R309-211-5

Adopted by Utah State Bulletin Number 2016-10, effective 5/1/2016
Amended by Utah State Bulletin Number 2019-3, effective 1/15/2018