37 Tex. Admin. Code § 259.356

Current through Reg. 49, No. 45; November 8, 2024
Section 259.356 - Lighting

Adequate illumination shall be provided throughout the cells and day rooms. An illumination level of 20 foot candles shall be provided at mirrors and tables. Master light controls for cells and day rooms and electrical conduit shall be out of reach of inmates. Inmates should be capable of controlling some lighting; override capability shall be provided. Security detention type lighting shall be provided in the inmate housing areas and vandal resistive lighting in inmate occupied areas. Night lights sufficient to permit continuous observation shall be provided. Control areas and means of egress shall be continuously illuminated. Exteriors of buildings and all entrances shall be lighted sufficiently to observe approaching persons.

37 Tex. Admin. Code § 259.356

The provisions of this §259.356 adopted to be effective April 4, 1999, 24 TexReg 2355