30 Tex. Admin. Code § 106.478

Current through Reg. 49, No. 44; November 1, 2024
Section 106.478 - Storage Tank and Change of Service

Any fixed or floating roof storage tank, or change of service in any tank, used to store chemicals or mixtures of chemicals shown in Table 478 in paragraph (8) of this section is permitted by rule, provided that all of the following conditions of this section are met:

(1) The tank shall be located at least 500 feet away from any recreational area or residence or other structure not occupied or used solely by the owner of the facility or the owner of the property upon which the facility is located.
(2) The true vapor pressure of the compound to be stored shall be less than 11.0 psia at the maximum storage temperature.
(3) For those compounds that have a true vapor pressure greater than 0.5 psia and less than 11.0 psia at the maximum storage temperature, any storage vessel larger than 40,000 gallons capacity shall be equipped with an internal floating cover or equivalent control.
(A) An open top tank containing an external floating roof using double seal technology shall be an approved control alternative equivalent to an internal floating cover tank, provided the primary seal consists of either a mechanical shoe seal or a liquid-mounted seal. Double seals having a vapor- mounted primary seal are an approved alternative for existing open top floating roof tanks undergoing a change of service.
(B) The floating cover or floating roof design shall incorporate sufficient flotation to conform to the requirements of American Petroleum Institute Code 650, Appendix C or an equivalent degree of flotation.
(4) Compounds with a true vapor pressure of 0.5 psia or less at the maximum storage temperature may be stored in a fixed roof or cone roof tank which includes a submerged fill pipe or utilizes bottom loading.
(5) For fixed or cone roof tanks having no internal floating cover, all uninsulated tank exterior surfaces exposed to the sun shall be painted chalk white except where a dark color is necessary to help the tank absorb or retain heat in order to maintain the material in the tank in a liquid state.
(6) Emissions shall be calculated by methods specified in Section 4.3 of the current edition of the United States Environmental Protection Agency Publication AP-42. This document may be obtained from the Superintendent of Documents, Washington D.C.20402. It is Stock Number 0550000251-7, Volume I.
(7) Before construction begins, storage tanks of 25,000 gallons or greater capacity and located in a designated nonattainment area for ozone shall be registered with the commission's Office of Permitting, Remediation, and Registration in Austin using Form PI-7. The registration shall include a list of all tanks, calculated emissions for each carbon compound in tons per year for each tank, and a Table 7 of Form PI-2 for each different tank design.
(8) Mixtures of the chemicals listed in Table 478 which contain more than a total of 1.0% by volume of all other chemicals not listed in Table 478 are not covered by this section.

Attached Graphic

30 Tex. Admin. Code § 106.478

The provisions of this §106.478 adopted to be effective March 14, 1997, 22 TexReg 2439; amended to be effective September 4, 2000, 25 TexReg 8653