Current through Register Vol. 51, page 56, November 4, 2024
Section 74:56:01:26 - Release detection requirements - Tank tightness testing and inventory reconciliation A combination of tank system tightness testing and product inventory reconciliation or another test of equivalent performance may be used to meet release detection requirements if they meet the following requirements:
(1) the tightness test testing is conducted at least once every five years until ten years after the tank is installed or upgraded under §§ 74:56:01:09 and 74:56:01:10, whichever is later, and the testing is capable of detecting a 0.1 gallon per hour leak rate with a probability of detection of 0.95 and a probability of false alarm of 0.05 from any portion of the UST system;(2) Inventory reconciliation or another test of equivalent performance is conducted monthly to detect a release of at least one percent of flow-through plus 130 gallons on a monthly basis, in the following manner: (a) Inventory volume measurements for regulated substance inputs, withdrawals, and the amount still remaining in the tank are recorded each operating day;(b) The equipment used is capable of measuring the level of product over the full range of the tank's height to the nearest 1/8 of an inch;(c) The regulated substance inputs are reconciled with delivery receipts by measurement of the tank inventory volume before and after delivery;(d) Deliveries are made through a drop tube that extends to within one foot of the tank bottom;(e) Product dispensing is metered and recorded within an accuracy of six cubic inches for every five gallons of product withdrawn; and(f) The measurement of any water level in the bottom of the tank is made to the nearest 1/8 of an inch at least once a monthS.D. Admin. R. 74:56:01:26
14 SDR 76, effective 11/29/1987; transferred from § 74:03:28:11, 18 SDR 62, effective 10/10/1991; transferred from § 74:03:28:11.01, July 1, 1996; 23 SDR 131, effective 2/24/1997; 44 SDR 192, effective 6/28/2018General Authority: SDCL 34A-2-93, 34A-2-99.
Law Implemented: SDCL 34A-2-98, 34A-2-99.