Section 61:15:05:09 - Automatic fire sprinkler requirements

An automatic sprinkler system must be installed when a basement utilized as a day care center exceeds 1,500 square feet in area. An automatic sprinkler system must be installed throughout the entire structure when a day care use occurs on a second story. An automatic sprinkler system must be installed in each day care center offering 24-hour care. The operation of any required automatic sprinkler system must automatically activate the fire alarm system. This section applies to new construction and any change of use.

S.D. Admin. R. 61:15:05:09

18 SDR 107, effective 1/1/1992; 33 SDR 113, effective 1/2/2007.

General Authority: SDCL 34-29B-2.

Law Implemented: SDCL 34-29B-2.