S.D. Admin. R. 44:80:03:04

Current through Register Vol. 51, page 67, December 16, 2024
Section 44:80:03:04 - Fire extinguisher equipment

Fire extinguisher equipment shall be installed and maintained by the following minimum standards:

(1) Portable fire extinguishers shall have a minimum rating of 2-A:10-B:C;
(2) Fire extinguisher equipment shall be inspected monthly and maintained yearly; and
(3) Approved fire extinguisher cabinets shall be provided throughout the building with one cabinet for each 3,000 square feet (278.7 square meters) of floor space or fraction thereof. The fire resistance rating of corridor walls shall be maintained at recessed fire extinguisher cabinets. The glazing in doors of fire extinguisher cabinets shall be safety glazing material. Fire extinguisher cabinets shall be identified with a sign mounted perpendicular to the wall surface above the cabinet or with sign mounted on the sides of cabinet that are visible from the corridor.

S.D. Admin. R. 44:80:03:04

42 SDR 51, effective 10/13/2015

General Authority: SDCL 34-12-13(3).

Law Implemented: SDCL 34-12-13(3).