Drinking fountains, fire extinguisher cabinets, and vending machines shall be located so they do not project into the required width of exit corridors. Handrails shall be installed with top 34 to 38 inches above the floor on both sides of the corridor and return to the wall at the ends. Handrails shall be installed with one and one half inch spacing between the wall and the handrail.
S.D. Admin. R. 44:79:10:12
General Authority: SDCL 34-12-13(1) and (3).
Law Implemented: SDCL 34-12-13(1) and (3).