S.D. Admin. R. 44:75:14:18

Current through Register Vol. 51, page 67, December 16, 2024
Section 44:75:14:18 - Air filters

Each ventilation system serving an operating room, delivery room, nursery, isolation room, laboratory sterile room, and the recirculated central air systems serving other hospital areas shall be equipped with a minimum of two filter beds. Filter bed number one shall be located upstream of the conditioning equipment and shall have a minimum efficiency of thirty percent. Filter bed number two shall be located downstream of the conditioning equipment and shall have a minimum efficiency of ninety percent. Central systems using one hundred percent outdoor air and serving other than sensitive areas shall be provided with filters rated at eighty percent efficiency. These filter efficiencies shall be warranted by the manufacturer and shall be based on the ASHRAE 52.2, 2007 edition, American Society of Heating, Refrigeration, and Air Conditioning Engineers dust spot test method with atmospheric dust. The exhausts from all laboratory hoods in which infectious or radioactive materials are processed shall be equipped with filters with a ninety-nie percent efficiency. Filter frames shall be durable and shall provide an airtight fit with the enclosing ductwork. All joints between filter segments and the enclosing ductwork shall have positive seal against air leakage.

S.D. Admin. R. 44:75:14:18

42 SDR 51, effective 10/13/2015; 50 SDR 062, effective 11/27/2023

General Authority: SDCL 34-12-13(2)(3)(14).

Law Implemented: SDCL 34-12-13(2)(3)(14).

ASHRAE 52.2, 2007 edition, American Society of Heating, Refrigeration, and Air Conditioning Engineers Copies are available at https://webstore.ansi.org/standards/ashrae/ashrae522017. Cost: $87.00.