S.D. Admin. R. 44:75:14:16

Current through Register Vol. 51, page 67, December 16, 2024
Section 44:75:14:16 - Details and finishes

Ceiling heights of operating rooms, delivery rooms, cystoscopic rooms, radiographic rooms, and rooms with ceiling-mounted surgical light fixtures shall be at least nine feet (2.74 meters).

The ceilings in isolation rooms, X-ray film processing rooms, central sterilization rooms, and operating rooms shall be an epoxy painted gypsum board membrane or an equivalent material for ease of cleaning and for improved maintenance of clean surfaces below the ceilings.

S.D. Admin. R. 44:75:14:16

42 SDR 51, effective 10/13/2015

General Authority: SDCL 34-12-13(3).

Law Implemented: SDCL 34-12-13(3).