S.D. Admin. R. 44:75:14:02

Current through Register Vol. 51, page 67, December 16, 2024
Section 44:75:14:02 - Newborn nursery unit

Each nursery shall provide a lavatory, emergency nurses call, oxygen, and facilities for viewing the babies. Each full-term nursery room may contain not more than 12 bassinets with a minimum area of 24 square feet (2.23 square meters) per bassinet. An examination and workroom with lavatory shall be provided and may serve up to 24 bassinets. A janitor's closet for storage of housekeeping supplies and equipment which contains a floor receptor or service sink shall be provided.

S.D. Admin. R. 44:75:14:02

42 SDR 51, effective 10/13/2015

General Authority: SDCL 34-12-13(1), (3), and (4).

Law Implemented: SDCL 34-12-13(1), (3), and (4).