Boiler rooms, food preparation centers, and laundries shall be insulated and ventilated to prevent any floor surface above them from exceeding a temperature of eighty-five degrees Fahrenheit or 29.4 degrees centigrade. All combustible insulation within the building shall be covered with a fire-resistive material giving fire protection equivalent to one half inch or 0.01 meters gypsum board, unless tested and acceptable by International Building Code, 2012 edition, section 2603.4 for use without a thermal barrier as installed.
S.D. Admin. R. 44:75:13:18
General Authority: SDCL 34-12-13(3).
Law Implemented: SDCL 34-12-13(3).
International Building Code, 2012 edition. Copies may be obtained from the International Code Council at https://shop.iccsafe.org/. Cost: $81.75.