Section 44:75:02:20 - Room required for isolation techniques

When an authorized facility personnel determines isolation is required, a private room with necessary equipment, including handwashing facilities, to carry out isolation techniques shall be provided. The room shall have a negative air pressure with regard to the corridor and connecting rooms and a minimum of six air exchanges an hour exhausted to the outside air.