S.D. Admin. R. 44:73:12:40

Current through Register Vol. 51, page 67, December 16, 2024
Section 44:73:12:40 - Receptacles or convenience outlets

Each resident bedroom shall have duplex receptacles as follows: one on each side of the head of each bed; receptacles for luminaires and motorized beds, if used; and one receptacle on each wall. Duplex receptacles for general use shall be installed approximately 50 feet apart in each corridor and within 25 feet of ends of corridors.

S.D. Admin. R. 44:73:12:40

42 SDR 51, effective 10/13/2015

General Authority: SDCL 34-12-13(4) and (14).

Law Implemented: SDCL 34-12-13(4) and (14).