Section 44:70:10:23 - Ducts

Each duct must be constructed of iron, steel, aluminum, or other approved metal or materials as defined in NFPA 101 Life Safety Code, 2012 edition, § 32.3.6.2.1. Duct linings, coverings, vapor barriers, and the adhesives used for applying them must have a flame spread index of not more than twenty-five and a smoke emission rating of not more than fifty using ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Materials. Each cold air duct must be insulated wherever necessary to maintain the efficiency of the system or to minimize condensation problems.

S.D. Admin. R. 44:70:10:23

38 SDR 115, effective 1/9/2012; 46 SDR 065, effective 11/26/2019; 50 SDR 019, effective 8/30/2023; 51 SDR 053, effective 11/11/2024

General Authority: SDCL 34-12-13.

Law Implemented: SDCL 34-12-13.

ASTM E84-23D, 2010 edition, Standard Test Method for Surface Burning Characteristics of Building Materials. Copies may be obtained at https://www.astm.org/e0084-23d.html. Cost: $119.00. NFPA 101 Life Safety Code, 2012 edition, National Fire Protection Association. Copies may be obtained at https://www.nfpa.org/product/nfpa-101-code/p0101code?Edition=2012&Language=English&Format=Softbound&type=digital. Cost: $160.00.