Current through Register Vol. 51, page 67, December 16, 2024
Section 44:70:03:03 - Fire extinguisher equipment Fire extinguisher equipment shall be installed and maintained by the following standards:
(1) Portable fire extinguishers shall have a minimum rating of 2-A:10-B:C;(2) Fire extinguisher equipment shall be inspected monthly and maintained yearly; and(3) Approved fire extinguisher cabinets shall be provided throughout the building with one cabinet for each 3,000 square feet (278.7 square meters) of floor space or fraction thereof The fire resistance rating of corridor walls shall be maintained at recessed fire extinguisher cabinets. The glazing in doors of fire extinguisher cabinets shall be wire glass or other safety glazing material. Fire extinguisher cabinets shall be identified with a sign mounted perpendicular to the wall surface above the cabinet.S.D. Admin. R. 44:70:03:03
Transferred from § 44:70:10:16 46 SDR 065, effective 11/26/2019General Authority: SDCL 34-12-13(3).
Law Implemented: SDCL 34-12-13(3).