Current through Register Vol. 51, page 67, December 16, 2024
Section 44:69:08:04 - Birth rooms for birth centers with three or more bedsEach birth room in a birth center with three or more beds shall meet the following requirements:
(1) Each birth room shall be a minimum of 200 square feet (18.40 square meters) including the newborn area;(2) Each birth room shall be equipped with a handwashing station with hands-free operators;(3) Each birth room shall have direct access to a private bathroom equipped with a handwashing sink, toilet, and shower or tub;(4) Each birth room shall be equipped with a vinyl floor surface;(5) Each birth room shall have adequate lighting with protective covers to prevent lamp from shattering;(6) Each birth room shall be equipped with battery operated emergency lighting;(7) Each birth room shall be located to ensure privacy during occupancy for labor, birth, and postpartum care until discharge from the center;(8) Each birth room shall be located out of the path of traffic and under direct supervision of birth center staff;(9) Each birth room shall have available oxygen and suction. Use of portable equipment is permitted;(10) Each birth room shall be provided with subdued indirect lighting and special lighting capable of providing at least 700 foot-candles in the delivery and newborn care area; and(11) If an elevator is provided, the elevator shall be equipped with a cab with a minimum dimensions of five feet eight inches wide by seven feet six inches deep (1.73 meters wide by 2.29 meters deep).S.D. Admin. R. 44:69:08:04
38 SDR 115, effective 1/9/2011.General Authority: SDCL 34-12-62(1) and (5).