Section 8-1249 - IRC R3901.4.2.1 Islands and peninsular countertops and work spacesReceptacle outlets shall be installed in accordance with the following: [210.52(C)(2)]
1. At least one receptacle outlet shall be provided for the first 6 feet (0.84m2), or fraction thereof, of the countertop or work surface. A minimum of two receptacle outlets shall be provided for any island over 6 feet long.2. At least one receptacle outlet shall be located within 2 feet (600 mm) of the outer end of a peninsular countertop or work surface. Additional receptacle outlets shall be permitted to be located as determined by the installer, designer or building owner. The location of the receptacle outlets shall be in accordance with Section E3901.4.3 [210.52(C)(2)(b)].Added by State Register Volume 46, Issue No. 05, eff. 5/27/2022.