S.C. Code Regs. § § 8-1220

Current through Register Vol. 48, No. 11, November 22, 2024
Section 8-1220 - IRC R404.1.9.2 Masonry piers supporting floor girders

Masonry piers supporting wood girders sized in accordance with Tables R602.7(1) and R602.7(2) shall be permitted in accordance with this section. Piers supporting girders for interior bearing walls shall be filled solidly with grout or type M or S mortar and shall have a minimum nominal dimension of 8 inches (203 mm) and a maximum height not exceeding 10 times the nominal thickness from the top of footing to bottom of sill plate or girder. Piers supporting beams and girders for exterior bearing walls shall be filled solidly with grout or type M or S mortar; shall contain a minimum of one #4 (13 mm) dowel mid-depth; and shall have a minimum nominal dimension of 8 inches (203 mm) and a maximum height of 4 times the nominal thickness from top of footing to bottom of sill plate or girder unless it can be shown by accepted engineering practice that there is sufficient foundation wall along the foundation line to resist the imposed lateral loads, in which case the maximum height shall not exceed 10 times the nominal thickness. Girders and sill plates shall be anchored to the pier or footing in accordance with Section R403.1.6 or Figure R404.1.5.3. Floor girder bearing shall be in accordance with Section R502.6.

S.C. Code Regs. § 8-1220

Added by State Register Volume 37, Issue No. 6, eff June 28, 2013; State Register Volume 40, Issue No. 06, eff. 6/24/2016; State Register Volume 43, Issue No. 05, eff. 5/24/2019; State Register Volume 44, Issue No. 06, eff. 6/26/2020; State Register Volume 46, Issue No. 05, eff. 5/27/2022.